CEILING CASSETTESPLIT TYPE AIR CONDITIONER(A Series)Model: IM-CKA-0501-ACSONCEILING CASSETTEINSTALLATION MANUAL
1-5EnglishMain Drain PipeFeed WaterFlexible Drain HoseDrain TestNOTEThis Indoor Unit uses a drain pump for condensed water drainage. Install the unit
1-6Indoor UnitCoolAirCeiling BoardPanelAir LeakGood InstallationBad InstallationNOTEInstall the front frame panel firmly to prevent cool air leakage w
1-7EnglishREFRIGERANT PIPING WORKRefrigerant piping is important in particular. Refrigeration cycle of the split air conditioner is realizedby the per
1-8ELECTRICAL WIRING CONNECTIONCK20A / CK25A & CK30AModel Indoor CK20A CK25A CK30AOutdoor SL20B/20C SL25B/25C SL28C/30CVoltage range** 220-240V/1P
1-9EnglishCK40A & CK50AModel Indoor 5CK30/40A CK40A CK50AOutdoor 5SL35C SL40C SL50CVoltage range** 380-420V/3Ph /50Hz+ N+ ! or 208-230V/3Ph/60Hz
1-10NNLOFA4WVCOMPNOF4WVCOMPNLECK40AR & CK50ARModel Indoor 5CK30/40AR CK40AR CK50AROutdoor 5SL35CR SL40CR SL50CRVoltage range** 380-420V/3Ph/50Hz
1-11EnglishSPECIAL PRECAUTIONS WHEN DEALING WITH R410A UNITR410A is a new HFC refrigerant which does not damage theozone layer. The working pressure o
1-12ASPECIAL PRECAUTIONS WHEN CHARGING UNIT WITHCOPELAND SCROLL COMPRESSORSThese precautions are intended for use with Copeland Scroll compressors onl
1-13EnglishShort Duct Specification• The indoor unit is provided with air discharge and air intake “knock-out” hole for duct connection. However the c
1-14OVERALL CHECKING• Ensure that :-1) The unit has been mounted solidly and rigid in position.2) Piping and connections are leak proof after charging
OUTLINE AND DIMENSIONS MODEL A B C D E F G H I J KCK / 5CK 20A/ARCK / 5CK 25A/ARCK / 5CK 30A/AR820 820 363 335 28 930 930 642 622 555 555CK 40A/AR(32
1-15EnglishAUTO RANDOM RE-START FUNCTIONIf there is a power cut when the unit is operating, it will automatically resume the same operating mode when
1-16If any malfunction of the air conditioner unit is noted, immediately switch off the power supply to the unit.Check the following fault conditions
OYL MANUFACTURING COMPANY SDN. BHD.JALAN PENGAPIT 15/19, P.O. BOX 7072, 40702 SHAH ALAM, SELANGOR DARUL EHSAN, MALAYSIA.• In the event that there is a
Outdoor Unit (SL - B Series)All dimensions are in mm / (in)Dimension A B C D E F G H J K L M N P Q R20B / 20BR840 646 330 297 309 626 41 85 75 177 106
Dimension A B C D E F G H I J K L M N O20C/CR 855 628 328 508 181 44 93 149 101 113 603 126 164 17 49(33,7) (24,7) (12,9) (20,0) (7,1) (1,7) (3,
iv! CautionSharp edges and coil surfaces are potential locations which may causeinjury hazards. Avoid from being in contact with these places.! Averti
1-1EnglishThis manual provides the procedures of installation to ensure a safe and good standard of operation for the airconditioner unit.Special adju
1-2CONTENTS- Outline And Dimensions page i – iv- Safety Precautions page 2- Installation Diagram page 3- Installation Of The Indoor Unit page 4- Insta
1-3EnglishIndoor unitOutdoor unitDrain HoseFront PanelAir Filter(behind the grille)Air Discharge LouverIR ReceiverLED LightAir Intake GrilleRefrigeran
1-4INSTALLATION OF THE INDOOR UNITPreliminary Site Survey• Electrical supply and installation is to conform to local authority's (e.g. National E